Features:
Safety Approval:
|
||
Terminal:
screw type connection: solid- 0.5 – 6 mm2 stranded- 0.5 – 4 mm2 Flat-type connection: 6.3×0.8
screw type connection: solid- 0.5 – 16 mm2 stranded- 0.5 – 10 mm2
All terminal block are labeling with numerical label |
Product Series | Rated Power | Dimension (mm) | Max. no. of terminals per side | Weight | |||||||
kVA | A | B | C | D | E | F | G | 24A | 44A | (kg) | |
TL490-400 | 0.04 | 70.0 | 76.0 | 56.0 | 42.0 | 50.0 | 4.8 | 8.0 | 6 | 4 | 1.1 |
TL490-630 | 0.063 | 77.0 | 84.0 | 78.0 | 64.0 | 64.0 | 4.8 | 8.5 | 7 | 4 | 1.6 |
TL490-101 | 0.1 | 77.0 | 84.0 | 78.0 | 64.0 | 64.0 | 4.8 | 8.5 | 7 | 4 | 2.1 |
TL490-161 | 0.16 | 87.0 | 96.0 | 101.0 | 86.0 | 84.0 | 5.8 | 10.0 | 8 | 4 | 2.85 |
TL490-251 | 0.25 | 87.0 | 96.0 | 101.0 | 86.0 | 84.0 | 5.8 | 10.0 | 8 | 4 | 3.7 |
TL490-311 | 0.31 | 96.0 | 105.0 | 103.0 | 85.6 | 80.2 | 5.8 | 12.0 | 8 | 4 | 4.3 |
TL490-401 | 0.4 | 105.0 | 117.0 | 102.0 | 85.0 | 90.0 | 5.8 | 12.0 | 10 | 6 | 5.1 |
TL490-501 | 0.5 | 105.0 | 117.0 | 121.0 | 104.0 | 90.0 | 5.8 | 12.0 | 10 | 6 | 6.6 |
TL490-631 | 0.63 | 137.0 | 152.0 | 110.0 | 90.0 | 122.0 | 7.0 | 15.0 | 14 | 8 | 8.0 |
TL490-801 | 0.8 | 137.0 | 152.0 | 126.0 | 106.0 | 122.0 | 7.0 | 15.0 | 14 | 8 | 10.2 |
TL490-102 | 1.0 | 137.0 | 152.0 | 154.0 | 134.0 | 122.0 | 7.0 | 15.0 | 14 | 8 | 13.4 |
TL490-162 | 1.6 | 149.0 | 171.0 | 150.0 | 126.0 | 145.0 | 7.0 | 15.0 | 16 | 10 | 19 |
TL490-202 | 2.0 | 149.0 | 171.0 | 170.0 | 146.0 | 145.0 | 7.0 | 15.0 | 16 | 10 | 23 |
TL490-252 | 2.5 | 165.0 | 190.0 | 188.0 | 164.0 | 160.0 | 9.0 | 16.0 | 16 | 10 | 27 |
Tolerance | typ | typ. | typ. | typ | typ | ±0.5 | ±1.0 | — | — | approx. |
Part Number Designation:
TL490 – XXX R YY – ZZS
Where XXX = Output Power (0.04kVA ~ 2.5kVA)
R = Input Style (“S” = Single; “D” = Double; “M” = multiple; “C” = Center Tapped)
YY = Input Voltage Range
ZZ = Output Voltage Range
S = Suffix for any alphanumeric or letter or blank for marketing purpose
Part No. | Rated Power | Short-Time Pating Power (PF=0.5) | Rated Input Voltage | Output Voltage (ZZ) V | |||||||||
(XXX) | kVA | kVA | (RYY) | V | (02) | (03) | (06) | (07) | (11) | (13) | (14) | (17) | |
24 | 42 | 110 | 115 | 230 | 2 x 110 | 2 x 115 | 2 x 230 | ||||||
TL490-XXXRYY-ZZ | (400) | 0.04 | —- | (S01)
(S02) (S03) (S04) (S05) (S06) (S07) (S08) (S09) (S10) (S11) (S12) (S13) (S14) (S15) (S16) (S17) (S18) (S19) |
100V
110V 115V 117V 120V 200V 220V 230V 240V 277V 300V 380V 400V 415V 440V 480V 500V 550V 600V |
· | · | · | · | · | · | · | · |
(630) | 0.063 | 0.19 | · | · | · | · | · | · | · | · | |||
(101) | 0.1 | 0.31 | · | · | · | · | · | · | · | · | |||
(161) | 0.16 | 0.49 | · | · | · | · | · | · | · | · | |||
(251) | 0.25 | 0.85 | · | · | · | · | · | · | · | · | |||
(311) | 0.31 | 1.12 | · | · | · | · | · | · | · | · | |||
(401) | 0.4 | 1.44 | · | · | · | · | · | · | · | · | |||
(501) | 0.5 | 2 | · | · | · | · | · | · | · | · | |||
(631) | 0.63 | 2.35 | · | · | · | · | · | · | · | · | |||
(801) | 0.8 | 3.4 | · | · | · | · | · | · | · | · | |||
(102) | 1 | 5 | · | · | · | · | · | · | · | · | |||
(162) | 1.6 | 7.3 | · | · | · | · | · | · | |||||
(202) | 2 | 9.7 | · | · | · | · | · | · | |||||
(252) | 2.5 | 13.3 | · | · | · | · | · | · |
Note: (1) The rated power is only applicable to transformers with separate windings. (not to
autotransformer).
(2) Short-time rating power is the most important selection criterion for control transformers.
This is required for switching on electromagnetic loads, the output voltage with this load
should not drop more than 5% in relation to the rated voltage in order to ensure safe switching.
(3) Other input voltage (600V max.) can be provided upon request.
(4) Other output voltage (600V max.) can be provided upon request.
(5) Other rated power (will not more than 20%) can be provided upon request.
Part No. | Rated Power | Short-Time Pating Power (PF=0.5) | Rated Input Voltage | Output Voltage (ZZ) V | |||||||||
(XXX) | kVA | kVA | (RYY) | V | (02) | (03) | (06) | (07) | (11) | (13) | (14) | (17) | |
24 | 42 | 110 | 115 | 230 | 2 x 110 | 2x 115 | 2 x 230 | ||||||
TL490-XXXRYY-ZZ | (400) | 0.04 | —- | (D01)
(D02) (D03) (D04) (D05) (D06) (D07) (D08) |
220-380V
230-400V 240-415V 254-440V 265-460V 277-480V 400-460V 550-575V |
· | · | · | · | · | · | · | · |
(630) | 0.063 | 0.19 | · | · | · | · | · | · | · | · | |||
(101) | 0.1 | 0.31 | · | · | · | · | · | · | · | · | |||
(161) | 0.16 | 0.49 | · | · | · | · | · | · | · | · | |||
(251) | 0.25 | 0.85 | · | · | · | · | · | · | · | · | |||
(311) | 0.31 | 1.12 | · | · | · | · | · | · | · | · | |||
(401) | 0.4 | 1.44 | · | · | · | · | · | · | · | · | |||
(501) | 0.5 | 2 | · | · | · | · | · | · | · | · | |||
(631) | 0.63 | 2.35 | · | · | · | · | · | · | · | · | |||
(801) | 0.8 | 3.4 | · | · | · | · | · | · | · | · | |||
(102) | 1 | 5 | · | · | · | · | · | · | · | · | |||
(162) | 1.6 | 7.3 | · | · | · | · | · | · | |||||
(202) | 2 | 9.7 | · | · | · | · | · | · | |||||
(252) | 2.5 | 13.3 | · | · | · | · | · | · |
Note: (1) The rated power is only applicable to transformers with separate windings. (not to
autotransformer).
(2) Short-time rating power is the most important selection criterion for control transformers.
This is required for switching on electromagnetic loads, the output voltage with this load
should not drop more than 5% in relation to the rated voltage in order to ensure safe switching.
(3) Other input voltage (600V max.) can be provided upon request.
(4) Other output voltage (600V max.) can be provided upon request.
(5) Other rated power (will not more than 20%) can be provided upon request.
Part No. | Rated Power | Short-Time Pating Power (PF=0.5) | Rated Input Voltage | Output Voltage (ZZ) V | |||||||||
(XXX) | kVA | kVA | (RYY) | V | (02) | (03) | (06) | (07) | (11) | (13) | (14) | (17) | |
24 | 42 | 110 | 115 | 230 | 2 x 110 | 2x 115 | 2 x 230 | ||||||
TL490-XXXRYY-ZZ | (400) | 0.04 | —- | (M01)
(M02) |
550- 525- 500- 480- 460- 440- 415- 400- 380- 230- 208V
600-575- 550-525- 500-480- 460-440- 415-400- 240-230V |
· | · | · | · | · | · | · | · |
(630) | 0.063 | 0.19 | · | · | · | · | · | · | · | · | |||
(101) | 0.1 | 0.31 | · | · | · | · | · | · | · | · | |||
(161) | 0.16 | 0.49 | · | · | · | · | · | · | · | · | |||
(251) | 0.25 | 0.85 | · | · | · | · | · | · | · | · | |||
(311) | 0.31 | 1.12 | · | · | · | · | · | · | · | · | |||
(401) | 0.4 | 1.44 | · | · | · | · | · | · | · | · | |||
(501) | 0.5 | 2 | · | · | · | · | · | · | · | · | |||
(631) | 0.63 | 2.35 | · | · | · | · | · | · | · | · | |||
(801) | 0.8 | 3.4 | · | · | · | · | · | · | · | · | |||
(102) | 1 | 5 | · | · | · | · | · | · | · | · | |||
(162) | 1.6 | 7.3 | · | · | · | · | · | · | |||||
(202) | 2 | 9.7 | · | · | · | · | · | · | |||||
(252) | 2.5 | 13.3 | · | · | · | · | · | · |
Note: (1) The rated power is only applicable to transformers with separate windings. (not to
autotransformer).
(2) Short-time rating power is the most important selection criterion for control transformers.
This is required for switching on electromagnetic loads, the output voltage with this load
should not drop more than 5% in relation to the rated voltage in order to ensure safe switching.
(3) Other input voltage (600V max.) can be provided upon request.
(4) Other output voltage (600V max.) can be provided upon request.
(5) Other rated power (will not more than 20%) can be provided upon request.
Part No. | Rated Power | Short-Time Pating Power (PF=0.5) | Rated Input Voltage | Output Voltage (ZZ) V | |||||||||
(XXX) | kVA | kVA | (RYY) | V | (02) | (03) | (06) | (07) | (11) | (13) | (14) | (17) | |
24 | 42 | 110 | 115 | 230 | 2 x 110 | 2x 115 | 2 x 230 | ||||||
TL490-XXXRYY-ZZ | (400) | 0.04 | —- |
(C01)
(C02)
(C03)
(C04)
|
550- 525- 500- 480- 460- 440- 415- 400- 380- 230- 208V
600-575- 550-525- 500-480- 460-440- 415-400- 240-230V
480-460- 440-415- 400-380- 230-208V
525-500- 480-460- 440-415- 400-240- 230V |
· | · | · | · | · | · | · | · |
(630) | 0.063 | 0.19 | · | · | · | · | · | · | · | · | |||
(101) | 0.1 | 0.31 | · | · | · | · | · | · | · | · | |||
(161) | 0.16 | 0.49 | · | · | · | · | · | · | · | · | |||
(251) | 0.25 | 0.85 | · | · | · | · | · | · | · | · | |||
(311) | 0.31 | 1.12 | · | · | · | · | · | · | · | · | |||
(401) | 0.4 | 1.44 | · | · | · | · | · | · | · | · | |||
(501) | 0.5 | 2 | · | · | · | · | · | · | · | · | |||
(631) | 0.63 | 2.35 | · | · | · | · | · | · | · | · | |||
(801) | 0.8 | 3.4 | · | · | · | · | · | · | · | · | |||
(102) | 1 | 5 | · | · | · | · | · | · | · | · | |||
(162) | 1.6 | 7.3 | · | · | · | · | · | · | |||||
(202) | 2 | 9.7 | · | · | · | · | · | · | |||||
(252) | 2.5 | 13.3 | · | · | · | · | · | · |
Note: (1) The rated power is only applicable to transformers with separate windings. (not to
autotransformer).
(2) Short-time rating power is the most important selection criterion for control transformers.
This is required for switching on electromagnetic loads, the output voltage with this load
should not drop more than 5% in relation to the rated voltage in order to ensure safe switching.
(3) Other input voltage (600V max.) can be provided upon request.
(4) Other output voltage (600V max.) can be provided upon request.
(5) Other rated power (will not more than 20%) can be provided upon request.
Available Schematics for single style input (S01~S19):
Terminal | Shorted | Terminal | Shorted | ||
Rated input Voltage | 1-3 | — | Rated input Voltage | 1-3 | — |
Rated input Voltage –5% | 1-2 | — | Rated input Voltage –5% | 1-2 | — |
Rated input Voltage +5% | 1-4 | — | Rated input Voltage +5% | 1-4 | — |
Rated output Voltage | 31-32 | — | Rated output Voltage (Series) | 31-34 | 32-33 |
Rated output Voltage (Parallel) | 31-34 | 31-32, 33-34 |
Note: (1) Input taps can be optional (for single / double style input only).
(2) No input tap for input (S19).
(3) For no input tap (without ±5%), the part number will add a suffix “N”
Available Schematics for double style input (D01~D08):
Terminal | Shorted | Terminal | Shorted | ||
Rated input Voltage LV | 2-4 | — | Rated input Voltage LV | 2-4 | — |
Rated input Voltage LV – ‘v’ | 3-4 | — | Rated input Voltage LV – ‘v’ | 3-4 | — |
Rated input Voltage LV + ‘v’ | 1-4 | — | Rated input Voltage LV + ‘v’ | 1-4 | — |
Rated input Voltage HV | 2-5 | — | Rated input Voltage HV | 2-5 | — |
Rated input Voltage HV – ‘v’ | 3-5 | — | Rated input Voltage HV – ‘v’ | 3-5 | — |
Rated input Voltage HV + ‘v’ | 1-5 | — | Rated input Voltage HV + ‘v’ | 1-5 | — |
Rated output Voltage | 31-32 | — | Rated output Voltage (Series) | 31-34 | 32-33 |
Rated output Voltage (Parallel) | 31-34 | 31-32, 33-34 |
Note: (1) Input taps can be optional (for single / double style input only).
(2) ‘v’ can be “15V” / “20V” / “25V”.
(3) For no input tap (without ‘v’), the part number will add a suffix “N”.
(4) For different ‘v’, the part number will add a unique suffix to represent:
“DA“ represent ‘v’ is 15V
“DB“ represent ‘v’ is 20V
“DC“ represent ‘v’ is 25V
Available Schematics for multiple style input (M01):
Terminal | Shorted | Terminal | Shorted | ||
Rated input Voltage: 550V | 1-8 | 4-5 | Rated input Voltage: 550V | 1-8 | 4-5 |
Rated input Voltage: 525V | 1-8 | 3-5 | Rated input Voltage: 525V | 1-8 | 3-5 |
Rated input Voltage: 500V | 1-8 | 2-5 | Rated input Voltage: 500V | 1-8 | 2-5 |
Rated input Voltage: 480V | 1-8 | 2-5 | Rated input Voltage: 480V | 1-8 | 2-5 |
Rated input Voltage: 460V | 1-8 | 4-6 | Rated input Voltage: 460V | 1-8 | 4-6 |
Rated input Voltage: 440V | 1-8 | 3-6 | Rated input Voltage: 440V | 1-8 | 3-6 |
Rated input Voltage: 415V | 1-8 | 3-7 | Rated input Voltage: 415V | 1-8 | 3-7 |
Rated input Voltage: 400V | 1-8 | 2-6 | Rated input Voltage: 400V | 1-8 | 2-6 |
Rated input Voltage: 380V | 1-8 | 2-7 | Rated input Voltage: 380V | 1-8 | 2-7 |
Rated input Voltage: 230V | 1-8 | 1-6, 4-8 | Rated input Voltage: 230V | 1-8 | 1-6, 4-8 |
Rated input Voltage: 208V | 1-8 | 1-7, 3-8 | Rated input Voltage: 208V | 1-8 | 1-7, 3-8 |
Rated output Voltage | 31-32 | — | Rated output Voltage (Series) | 31-34 | 32-33 |
Rated output Voltage (Parallel) | 31-34 | 31-32, 33-34 |
Available Schematics for multiple style input (M02):
Terminal | Shorted | Terminal | Shorted | ||
Rated input Voltage: 600V | 1-8 | 4-5 | Rated input Voltage: 600V | 1-8 | 4-5 |
Rated input Voltage: 575V | 1-8 | 4-6 | Rated input Voltage: 575V | 1-8 | 4-6 |
Rated input Voltage: 550V | 1-8 | 4-7 | Rated input Voltage: 550V | 1-8 | 4-7 |
Rated input Voltage: 525V | 1-8 | 3-5 | Rated input Voltage: 525V | 1-8 | 3-5 |
Rated input Voltage: 500V | 1-8 | 3-6 | Rated input Voltage: 500V | 1-8 | 3-6 |
Rated input Voltage: 480V | 1-8 | 3-7 | Rated input Voltage: 480V | 1-8 | 3-7 |
Rated input Voltage: 460V | 1-8 | 3-7 | Rated input Voltage: 460V | 1-8 | 3-7 |
Rated input Voltage: 440V | 1-8 | 2-5 | Rated input Voltage: 440V | 1-8 | 2-5 |
Rated input Voltage: 415V | 1-8 | 2-6 | Rated input Voltage: 415V | 1-8 | 2-6 |
Rated input Voltage: 400V | 1-8 | 2-7 | Rated input Voltage: 400V | 1-8 | 2-7 |
Rated input Voltage: 240V | 1-8 | 1-7, 3-8 | Rated input Voltage: 240V | 1-8 | 1-7, 3-8 |
Rated input Voltage: 230V | 1-8 | 1-7, 3-8 | Rated input Voltage: 230V | 1-8 | 1-7, 3-8 |
Rated output Voltage | 31-32 | — | Rated output Voltage (Series) | 31-34 | 32-33 |
Rated output Voltage (Parallel) | 31-34 | 31-32, 33-34 |
Available Schematics for center tapped style input (C01):
Terminal | Shorted | Terminal | Shorted | ||
Rated input Voltage: 550V | 1-7 | — | Rated input Voltage: 550V | 1-7 | — |
Rated input Voltage: 525V | 2-7 | — | Rated input Voltage: 525V | 2-7 | — |
Rated input Voltage: 500V | 3-7 | — | Rated input Voltage: 500V | 3-7 | — |
Rated input Voltage: 480V | 1-6 | — | Rated input Voltage: 480V | 1-6 | — |
Rated input Voltage: 460V | 2-6 | — | Rated input Voltage: 460V | 2-6 | — |
Rated input Voltage: 440V | 3-6 | — | Rated input Voltage: 440V | 3-6 | — |
Rated input Voltage: 415V | 1-5 | — | Rated input Voltage: 415V | 1-5 | — |
Rated input Voltage: 400V | 2-5 | — | Rated input Voltage: 400V | 2-5 | — |
Rated input Voltage: 380V | 3-5 | — | Rated input Voltage: 380V | 3-5 | — |
Rated input Voltage: 230V | 2-4 | — | Rated input Voltage: 230V | 2-4 | — |
Rated input Voltage: 208V | 3-4 | — | Rated input Voltage: 208V | 3-4 | — |
Rated output Voltage | 31-32 | — | Rated output Voltage (Series) | 31-34 | 32-33 |
Rated output Voltage (Parallel) | 31-34 | 31-32, 33-34 |
Available Schematics for center tapped style input (C02):
Terminal | Shorted | Terminal | Shorted | ||
Rated input Voltage: 600V | 1-7 | — | Rated input Voltage: 600V | 1-7 | — |
Rated input Voltage: 575V | 2-7 | — | Rated input Voltage: 575V | 2-7 | — |
Rated input Voltage: 550V | 3-7 | — | Rated input Voltage: 550V | 3-7 | — |
Rated input Voltage: 525V | 1-6 | — | Rated input Voltage: 525V | 1-6 | — |
Rated input Voltage: 500V | 2-6 | — | Rated input Voltage: 500V | 2-6 | — |
Rated input Voltage: 480V | 3-6 | — | Rated input Voltage: 480V | 3-6 | — |
Rated input Voltage: 460V | 1-5 | — | Rated input Voltage: 460V | 1-5 | — |
Rated input Voltage: 440V | 2-5 | — | Rated input Voltage: 440V | 2-5 | — |
Rated input Voltage: 415V | 3-5 | — | Rated input Voltage: 415V | 3-5 | — |
Rated input Voltage: 400V | 3-5 | — | Rated input Voltage: 400V | 3-5 | — |
Rated input Voltage: 240V | 1-4 | — | Rated input Voltage: 240V | 1-4 | — |
Rated input Voltage: 230V | 2-4 | — | Rated input Voltage: 230V | 2-4 | — |
Rated output Voltage | 31-32 | — | Rated output Voltage (Series) | 31-34 | 32-33 |
Rated output Voltage (Parallel) | 31-34 | 31-32, 33-34 |
Available Schematics for center tapped style input (C03):
Terminal | Shorted | Terminal | Shorted | ||
Rated input Voltage: 480V | 1-6 | — | Rated input Voltage: 480V | 1-6 | — |
Rated input Voltage: 460V | 2-6 | — | Rated input Voltage: 460V | 2-6 | — |
Rated input Voltage: 440V | 3-6 | — | Rated input Voltage: 440V | 3-6 | — |
Rated input Voltage: 415V | 1-5 | — | Rated input Voltage: 415V | 1-5 | — |
Rated input Voltage: 400V | 2-5 | — | Rated input Voltage: 400V | 2-5 | — |
Rated input Voltage: 380V | 3-5 | — | Rated input Voltage: 380V | 3-5 | — |
Rated input Voltage: 230V | 2-4 | — | Rated input Voltage: 230V | 2-4 | — |
Rated input Voltage: 208V | 3-4 | — | Rated input Voltage: 208V | 3-4 | — |
Rated output Voltage | 31-32 | — | Rated output Voltage (Series) | 31-34 | 32-33 |
Rated output Voltage (Parallel) | 31-34 | 31-32, 33-34 |
Available Schematics for center tapped style input (C04):
Terminal | Shorted | Terminal | Shorted | ||
Rated input Voltage: 525V | 1-6 | — | Rated input Voltage: 525V | 1-6 | — |
Rated input Voltage: 500V | 2-6 | — | Rated input Voltage: 500V | 2-6 | — |
Rated input Voltage: 480V | 3-6 | — | Rated input Voltage: 480V | 3-6 | — |
Rated input Voltage: 460V | 1-5 | — | Rated input Voltage: 460V | 1-5 | — |
Rated input Voltage: 440V | 2-5 | — | Rated input Voltage: 440V | 2-5 | — |
Rated input Voltage: 415V | 3-5 | — | Rated input Voltage: 415V | 3-5 | — |
Rated input Voltage: 400V | 3-5 | — | Rated input Voltage: 400V | 3-5 | — |
Rated input Voltage: 240V | 1-4 | — | Rated input Voltage: 240V | 1-4 | — |
Rated input Voltage: 230V | 2-4 | — | Rated input Voltage: 230V | 2-4 | — |
Rated output Voltage | 31-32 | — | Rated output Voltage (Series) | 31-34 | 32-33 |
Rated output Voltage (Parallel) | 31-34 | 31-32, 33-34 |
Product Catalog | |