[][] | Features:
Safety Approval:
|
Physical Dimension :
Product Series | Dimension (mm) | Weight (g) | ||||
A | B | C | D | E | ||
TL315-AYYY-ZZZ | 84.0 | 94.0 | 63.0 | 45.0 | 61.5 | 700 |
TL315-BYYY-ZZZ | 98.0 | 94.0 | 63.0 | 45.0 | 61.5 | 900 |
TL315-CYYY-ZZZ | 109.0 | 104.0 | 63.0 | 45.0 | 70.0 | 1250 |
TL315-DYYY-ZZZ | 165.0 | 94.0 | 63.0 | 45.0 | 61.5 | 1900 |
Tolerance | ±1.0 | ±1.0 | ±1.0 | ±0.5 | ±0.5 | approx. |
Note: Stable plastic enclosure for panel installation on mounting rails (DIN EN50022).
Order Part Number | Power Rating | I/P Voltage (50/60Hz) (V) | O/P Rated Voltage (V) | O/P Rated Current (A) | Sec Fuse Rating (A) | Regulation (%) typ | Ripple Factor (%) typ | Efficiency (%) typ | Dielectric Strength (kVrms) | Electrical Schematic |
TL315-A020-24* TL315-A025-24* TL315-B030-24* TL315-B036-24* TL315-C050-24* TL315-C063-24* TL315-D080-24* TL315-D100-24* | 20VA 25VA 30VA 36VA 50VA 63VA 80VA 100VA |
230 230 230 230 230 230 230 230 |
24Vrms 24Vrms 24Vrms 24Vrms 24Vrms 24Vrms 24Vrms 24Vrms |
0.83 1.04 1.25 1.50 2.08 2.63 3.33 4.17 |
1 1.25 1.25 1.6 2.5 3.15 4 5 |
13.5 15.5 9.5 10.5 9.0 10.5 9.5 11.5 |
— — — — — — — — |
81 81 85 85 87 87 87 86 |
4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 |
I I I I I I II II |
TL315-A016-12* TL315-A016-24* TL315-B024-12* TL315-B024-24* TL315-C032-12* TL315-C036-24* TL315-D048-12* TL315-D048-24* TL315-D060-24* |
16W 16W 24W 24W 32W 36W 48W 48W 60W |
230 230 230 230 230 230 230 230 230 |
12Vdc 24Vdc 12Vdc 24Vdc 12Vdc 24Vdc 12Vdc 24Vdc 24Vdc |
1.33 0.67 2.00 1.00 2.66 1.50 4.00 2.00 2.50 |
1.6 0.8 2 1 3.15 1.6 4 2 2.5 |
31 30 28 23.5 26 23 30 21 23.5 |
5 3 5 3 5 3 5 3 3 |
70 73 75 78 75 79 74 77 79 |
4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 |
III III III III III III IV IV IV |
Remark : “*” mean
Note:
1. Fully cast-resin molded transformer
2. For panel installation on mounting rails (DIN EN 50022)
3. Input and output with screw-type terminals.
4. Protection index: IP20
5. Secondary side with ON/OFF switch and replaceable fuse
(DIA5 x 20mm / IEC-60127-2 / slow blow)
6. Unit is for indoor use and must have all terminations well-protected by plastic cover or in a panel/enclosure
Circuit Diagrams :
Product Catalog | |
Power-Supply-For-Panel-Installation-On-Mounting-Rails |